Passer au contenu principal Passer à la recherche Passer à la navigation principale

P44000 Temperature Transmitter | Input Pt100 resistance thermometer (RTD) | High isolation up to 6600V

Description

P44000 Temperature Transmitter | Input Pt100 resistance thermometer (RTD) | High isolation up to 6600V
Precise Temperature Measurement at High Voltage Potentials up to 6 kV
  • Transmitter for Pt100 temperature sensors, 2- or 4-wire connection
  • Fixed range models for 0 to 150 °C, 0 to 200 °C and 0 to 300 °C input ranges
  • Impressed output current of 4 to 20 mA
  • Compact 67.5 and 22.5 mm modular housings based on proven VariTrans technology
  • High isolation up to 6 kV AC/DC basic insulation and up to 2.5 kV AC/DC reinforced insulation with overvoltage category III and pollution degree 2 according to EN 50178 (input against output and power supply)
  • 22.5 mm housing for less demanding isolation requirements up to 2 kV AC/DC (basic insulation)
  • Low measurement error of just ± 1 K (typically ± 0.5 K) and short T90 delay time of 100 ms
  • VariPower broad-range power supply for 20 … 253 V AC/DC ensures safe operation even with unstable power grids
  • Resistant to environmental influences through vacuum encapsulation
  • Suitable for extreme environments: ambient temperature during operation –40 … +85 °C
  • 5-year warranty

When temperatures are to be measured using Pt100 resistance thermometers in high-voltage environments, standard temperature transmitters are often unsuitable due to their insufficient insulation.

Resistance thermometers can be insulated against high voltage. In practice, however, the available installation space is often too small. Moreover, the insulation is weakened by thermal and mechanical aging.

For temperature measurement on power electronics components, maximum safety is therefore provided by high-voltage resistant galvanic isolation. A typical application is the monitoring of the winding temperature of electric motors, generators or transformers.

The Solution:
Pt100 Transmitter With 6 kV AC/DC Basic Insulation

The new ProLine P 44000 transmitter for high-voltage applications converts the resistance of a 2- or 4-wire Pt100 resistance thermometer into a 4 to 20 mA signal with high accuracy and short delay times.

The output signal is galvanically isolated from the input signal and the voltage supply. The isolation is designed for working voltages of up to 6 kV AC/DC. During routine testing, the test voltage is 15 kV AC. Vacuum encapsulation protects the circuit against environmental influences and ensures that the extraordinary isolation properties are maintained.

The product line covers the standard ranges of 0 to 150 °C, 0 to 200 °C and 0 to 300 °C. The transmitters are available in 67.5 and 22.5 mm modular housings to suit different requirements.

Condition Monitoring of High-Voltage Motors

Having an active predictive maintenance campaign in place for large rotating equipment can be a key strategy for maximizing process uptime.

Nous attendons avec impatience votre réponse!
Nous Contacter

Détails techniques

Alimentation électrique: 24 V CA, 24 V CC, 110 / 115 V CA, 220 / 230 V CA, Bloc d'alimentation à plage élargie
Catégorie de produits: Amplificateur séparateur haute tension, Convertisseur de mesure
Fréquence limite: < 1 kHz
Gamme de produits: ProLine
Tension d'essai: 2,5 kV, 5 kV, 10 kV, 15 kV, 510 V
Type d'appareil: Convertisseurs de température
Entrée: Thermomètres à résistance 
Sortie: 4 … 20 mA
Tension de service min.: 50 V, 300 V, 1000 V, 2000 V, 3600 V, 4800 V, 6600 V
Classe d'erreur: < 0,5 %
Boîtier: Boîtier série 17,5 … 67,5 mm

Téléchargements

Manuals

[15] User Manual (DE, EN, FR, BR)
P44000
Version 03

Brochures

[18014] Brochure
Appareils de précision
pour l’industrie ferroviaire
[14160] Brochure
Aperçu des produits Technologie d'interface

Fiches techniques

[12258] Fiche technique
P44000
Description du produit | Caractéristiques techniques | Gamme de produits

Certificats

[12063] EU Declaration of Conformity (DE, EN, FR)
No. EU220125L | 2022-11-25
P44000 (P441**D1-nnnn, P442**D3-nnnn)
[12071] Certificate of Compliance (UL)
P41000, P42000, P43000, P44200, P51000, P52000
MOTOR CONTROLLER ACCESSORIES OVER 1500 VOLTS
No. UL-US-L356768-11-22503102-1 | 202406-28

Notre service

Lorem lorem ipsum ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet. Lorem ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet.

Utilisé dans les processus ou les applications

Amplificateurs séparateurs haute tension et convertisseurs de mesure pour l’acquisition et la conversion de signaux de courant, de tension, de température, de régime, de dilatation et de résistance.
La technologie de mesure électrique de Knick offre de nombreuses solutions pour la détection et la conversion de signaux ainsi que pour la mesure du courant, de la tension et bien plus encore.

Articles de blog pertinents

Robust WA111 Retractable Fitting Made of Plastic for Highly Corrosive Operating Conditions

The plastic WA111 retractable fitting is a robust and cost-effective solution for corrosive processes and environments. It is equipped with a secure lock function and multiple nozzles for thorough sensor cleaning.

Coopération réussie : Knick a développé un support rétractable spécial Ceramat WA 155 pour les sondes optiques de SOPAT.

Nettoyage automatique des sondes optiques dans les processus d'encrassement : Un projet commun de Knick et SOPAT pour une application client avec Ceramat.

Canne d’immersion haute qualité pour applications mobiles

Avec l’ARD 170, Knick propose une canne d’immersion haute qualité pour mesures mobiles du pH, de la conductivité et de l’oxygène dissous. Les développeurs ont accordé une attention particulière à la simplicité et la flexibilité d’utilisation.

Canne d'immersion modulaire en version électriquement conductrice

Avec ses cannes d'immersion ARD 50 EL et ARD 75 EL, Knick complète de deux versions électriquement conductrices (EL) son portefeuille de cannes d’analyse de liquides. Les modulaires permettent l’utilisation de sondes spécifiques aux applications.

How to get the sensor into the process

Sensors as the direct interface to the process must be exactly matched to the chemistry of the measured medium and to the prevailing pressure and temperature conditions.