跳到主要内容 跳到搜索 跳到主导航

P43000 TRMS AC/DC High Voltage Transducer | Input up to ±5 A | True RMS measurement

Description

P43000 TRMS AC/DC High Voltage Transducer | Input up to ±5 A | True RMS measurement
  • Universal usability:
    • AC input 100 mA~ to 5 A~
    • DC output 0 (4) … 20 mA, 0 … 10 V
  • Working voltages up to 3600 V AC/DC
  • TransShield technology
    allows for extremely compact modular housing
  • Protection against electric shock 
    through protective separation up to 1800 V AC /DC according to EN 61140
  • Test voltages up to 15 kV AC
  • Outstanding transmission properties:
    • Gain error < 0.5 % with crest factor < 3
    • Gain error < 1 % with crest factor 3 … 5
    • Response time T90
  • Virtually no influence from common-mode voltages:
    CMRR approx. 150 dB
  • Tremendous flexibility thanks to:
    • calibrated switching of up to 16 input/output ranges
    • up to 16 customer-specific ranges
    • VariPower broad-range power supply 20 V to 253 V AC/DC
  • Reliable function even with unstable supply
  • No damage
    in the case of erroneous power connection
  • Switchable models
    reduce variety of versions, thus saving storage costs
  • Robust
    thanks to vacuum encapsulation
  • Mechanically stable
    for operation on ships, trains and vehicles
  • 5-year warranty

The P43000 TRMS isolation amplifiers have been specially conceived for measurements of bipolar currents ranging from milliamps up to 5 amps. They reliably isolate high potentials at the input circuit. Thanks to the true rms conversion in the transducer, even distorted input signals are captured correctly and output as so-called true rms values.


The isolating distances are designed to withstand permanent voltages up to 3600 V AC/DC and fast transients up to 20 kV.

我们期待您的来信
联系我们

技术细节

产品类别: 高压隔离放大器
产品系列: ProLine
截止频率: < 1 kHz
最小工作电压: 50 V, 300 V, 1000 V, 2000 V, 3600 V
最小测试电压: 2,5 kV, 5 kV, 10 kV, 15 kV, 510 V
电源: 24 V AC, 24 V DC, 110 / 115 V AC, 220 / 230 V AC, 其他, 宽范围电源
设备类型: AC/DC 测量变送器, 通用隔离放大器, 高压隔离放大器
输入: > (±)100 mA ( … kA)
输出: 0 … 10 V, 0 … 20 mA, 4 … 20 mA, ±10 V, ±20 mA, 其他
误差级别: < 0.5 %
结构型式: 17.5 … 67.5 mm 模块化外壳

下载

Manuals

[17399] 操作说明书
P43000 TRMS
Version 06

小册子

[14160] 手册
产品总览 接口技术

数据手册

[1615] 数据表
P43000 TRMS
产品描述 | 规格 | 产品范围

证书

[12429] EU Declaration of Conformity (DE, EN, FR)
P4*000 KTA
No. EU230522A | 2023-12-12
[11463] EU Declaration of Conformity (DE, EN, FR)
Series VariTrans P4x000 (D*-nnnn/D*AG-nnnn/D*TRMS-nnnn)
No. EU221209A | 2023-11-29
[14140] Quality Report (MTBF)
Document No. TX180416A
Failure Rate of Series P40000

Software

[11876] Knick Produktmakros (.pdf)
ePLAN Electric P8
[12154] Software (.zip)
ePLAN P8 Produktmakros

我们的服务

Lorem lorem ipsum ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet. Lorem ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet.

在工艺或应用中使用

相关的博客文章

Robust WA111 Retractable Fitting Made of Plastic for Highly Corrosive Operating Conditions

The plastic WA111 retractable fitting is a robust and cost-effective solution for corrosive processes and environments. It is equipped with a secure lock function and multiple nozzles for thorough sensor cleaning.

成功的聯合專案: 尼克公司開發了特殊的塞拉馬特 WA 155 可伸縮配件, 用於 SOPAT 的光學探頭

污染過程中光學探頭的自動清潔:尼克斯和 SOPAT 與 Ceramat 客戶應用的聯合專案

适合移动应用场景的高品质浸入式连接件

Knick Elektronische Messgeräte GmbH & Co. KG 公司向市场上推出的 ARD 170 是一款高品质浸入式连接件,用于移动式测量 pH 值、电导率和溶解氧。在进行结构设计时,特别注意简单灵活的操作方式。

导电版模块化浸入式连接件

Knick Elektronische Messgeräte GmbH & Co. KG 公司借助浸入式连接件 ARD 50 EL 和 ARD 75 EL 在自己的液体分析连接件产品组合中增加了导电 (EL) 版。这两种工业连接件具有模块化结构,可以广泛选择各种专用传感器。

How to get the sensor into the process

Sensors as the direct interface to the process must be exactly matched to the chemistry of the measured medium and to the prevailing pressure and temperature conditions.